Fire alarm voltage drop calculator (NAC circuits)

Estimate the cable voltage loss on a two-wire notification appliance circuit. The default method places all load at the end of a single radial run. For the same fixed current, this gives at least as much cable loss as placing devices along that run.

Circuit inputs

Results update as you type. Use listed maximum alarm current for the selected device settings and supply waveform. 1 mA = 0.001 A.

24 V is a nominal starting value. Enter available NAC terminal voltage for the operating condition being checked.

16 V is an editable example, not a universal requirement. For mixed devices, use the highest listed minimum.

20.4 V is a common end-of-discharge design value. Enter the voltage at the NAC terminals after panel and power-supply losses, not the raw battery voltage.

Requires equal-current devices at L/N, 2L/N, …, L from the source. Mixed currents or unequal spacing need a segment-by-segment calculation.

Tool ranges: 0–100,000 ft (0–30,480 m), 0–100 A, voltages above 0 up to 100 V, and up to 10,000 devices in 100 groups. These are input limits, not equipment ratings.

Exports use your current inputs. The Excel workbook includes live formulas: change its blue input cells to recalculate.

Calculated results

Total load: 1.5 A. Loop resistance: 1.843 Ω (outgoing plus return).

Using 3.071 Ω/1,000 ft per conductor at 75 °C. Pass/fail uses unrounded values; displays are rounded.

Source check: 24 V

All load at the end (conservative)

PASS against the entered minimum only.

Voltage drop
2.764 V (11.517% of 24 V)
Voltage at last device
21.236 V
Maximum length for this load
868.255 ft one way

Battery-condition check is off. Turn it on to see the circuit at end of discharge.

Studying for NICET FA II? Take the free 10-question check to see exactly which topics to fix first, then close the gaps with the Alarm Ladder course.

Or read a full free lesson first (no signup).

Studying with a coworker? Send them the free check.

Fire alarm voltage drop calculator (NAC circuits)

Check inputs: Prepare this worksheet using the Print command.

Need a fire alarm voltage drop calculator for Excel? Download a free .xlsx calculation spreadsheet with live formulas, then change the blue input cells in Excel to recalculate resistance, voltage drop and last-device voltage. The CSV export contains your current inputs and results. Both include the calculation-aid notice and resistance citation.

By the Alarm Ladder editorial team.

How to use the voltage drop calculator

Run it when you lay out a notification appliance circuit, again whenever appliances are added or candela settings change on an existing one, and before the plans go to the AHJ.

  1. Enter the one-way cable length from the NAC terminals to the last appliance, measured along the real route with risers and drops. The calculator doubles it for the return conductor.
  2. Pick the wire gauge and solid or stranded copper. Compare our calculated resistance in the table below with your cable's data sheet.
  3. Enter the alarm load as one total current or as a device list. Use each appliance's maximum listed current for the candela, tone and voltage it will run at.
  4. Enter the voltage at the NAC terminals and the highest listed minimum among the appliances on the circuit. Tick the battery check and enter the end-of-discharge voltage from your panel manual.
  5. Read the last-device voltage, the PASS or FAIL against your minimum and the longest one-way run that still passes. Print the worksheet or download the Excel workbook for the submittal.

The fire alarm voltage drop formula guide derives every step and works a segment-by-segment example. New to the circuit itself? Start with the NAC circuit guide.

How the calculation works

First establish the voltage budget: subtract the device's listed minimum from the voltage available at the NAC terminals in the supply condition being checked. Obtain the maximum alarm current for the selected appliance settings and waveform from its installation instructions. Repeat the check for the battery condition; nominal panel voltage alone does not describe that condition.

Let L be one-way length in feet, r the resistance of one conductor in Ω per 1,000 ft at 75 °C, I the total alarm load in amperes, Vₛ the voltage available at the circuit source, and Vₘᵢₙ the device minimum from its listing. Convert meters to feet using L(ft) = L(m) ÷ 0.3048.

  • Loop resistance: Rₗₒₒₚ = 2 × L × r ÷ 1,000.
  • Cable voltage drop: ΔV = I × Rₗₒₒₚ.
  • Drop percentage: 100 × ΔV ÷ Vₛ.
  • Voltage at the last device: Vₗₐₛₜ = Vₛ − ΔV.
  • Pass for the entered minimum: Vₗₐₛₜ ≥ Vₘᵢₙ.
  • Maximum one-way length: Lₘₐₓ = 1,000 × (Vₛ − Vₘᵢₙ) ÷ (2 × I × r), for I > 0 and Vₛ ≥ Vₘᵢₙ.

These equations apply Ohm's law as applied in System Sensor's voltage-drop example, p. 4 to the outgoing and return conductors. If the source is already below the device minimum, no length passes. At zero current there is no finite voltage-drop length limit in this model.

Optional distributed-load estimate

For N equal-current devices equally spaced at L/N, 2L/N, …, L, each segment carries the current of the devices downstream. Summing those segment drops gives:

ΔVdistributed = (2 × r × L / 1,000) × (I / N²) × (1 + 2 + … + N) = ΔVlumped × (N + 1) / (2N)

The maximum length is Lₘₐₓ from the lumped formula divided by (N + 1)/(2N). One device gives the lumped result; ten give 55% of the lumped drop. The factor approaches one-half as N increases, but simply halving the drop is inaccurate for a small device count.

This is an algebraic extension of the same I × R cable-loss method: calculate each segment with its downstream current, then add the losses. The optional estimate assumes equal currents and equal spacing; use an actual segment-by-segment design for different spacing, mixed currents, or branches.

Worked example

For 14 AWG solid uncoated copper, a 300 ft one-way run, and 1.5 A total load, the calculated resistance at 75 °C is approximately 3.071293 Ω/1,000 ft. The loop resistance is 2 × 300 × 3.071293 ÷ 1,000 = 1.842776 Ω. Drop is 1.5 × 1.842776 = 2.764164 V.

At a 24 V source, the last device receives approximately 21.236 V, an 11.517% drop, which passes an entered 16 V minimum. Maximum one-way length is approximately 868.255 ft. At a 20.4 V battery-condition source, the same load leaves 17.636 V at the last device and limits length to approximately 477.540 ft.

For ten equal-current devices evenly spaced over that same 300 ft, the optional estimate gives 2.764164 × 11/20 = 1.520290 V drop. These are fictional calculation inputs, not an equipment specification or exam question.

Worked example: passes on 24 V, fails on battery

An invented hallway NAC has 8 horn-strobes at 0.12 A and 4 strobes at 0.09 A, all maximum listed currents for the chosen settings. Enter them as a device list: 0.96 A + 0.36 A = 1.32 A. The run is 400 ft one way on 16 AWG stranded copper, the highest listed minimum is 16 V, and the panel manual gives 20.4 V at end of battery discharge.

  1. Resistance: the calculator gives 4.9812 Ω per 1,000 ft for 16 AWG stranded, so the loop is 2 × 400 × 4.9812 ÷ 1,000 = 3.985 Ω.
  2. Drop: 1.32 A × 3.985 Ω = 5.260 V.
  3. On 24 V the last appliance gets 18.740 V. PASS.
  4. On 20.4 V it gets 15.140 V, a 25.8% drop. FAIL. The longest passing run on battery is 334.59 ft.

Fix one: move to 14 AWG stranded. The drop falls to 3.308 V, the last appliance gets 17.092 V on battery, and the run could reach 532.02 ft. Fix two: keep 16 AWG and split the devices over two NACs of 4 horn-strobes and 2 strobes each, 0.66 A per circuit. If both runs are still 400 ft, each drops 2.630 V and the last appliance gets 17.770 V on battery. Every figure above is the calculator's own output for these inputs. The fire alarm wire size calculator compares all five gauges in one pass.

Copper reference data at 75 °C

Calculated from NBS Handbook 100, Copper Wire Tables: ρ₂₀ = 1/58 Ω·mm²/m and α₂₀ = 0.00393/°C (appendix 5, printed p. 40); AWG geometry (§2.2, p. 6); stranded allowance (appendix 4, p. 38).

d(mm) = 0.127 × 92^((36 − AWG)/39); A = πd²/4; r₂₀ = ρ₂₀ × 304.8/A; r₇₅ = r₂₀ × [1 + 0.00393 × (75 − 20)].

Multiply by 1.02 for the handbook's concentric-lay stranded estimate. These calculated values use ideal annealed, uncoated copper; they are not a cable manufacturer's maximum resistance specification. Actual stranding, tolerances and construction can change resistance. Confirm against your cable's published data. The 75 °C assumption does not establish cable suitability.

For a code-book comparison, open NFPA 70-2020, Chapter 9, Table 8 and its notes in your own copy. Match material, coating, construction, units and temperature before comparing resistance. This tool retains the NBS calculation; it does not import or reproduce NEC table entries. Use the cable manufacturer's resistance for a project calculation when specified.

The coefficient above starts at 20 °C. The 20-to-75 °C multiplier is 1 + 0.00393 × 55 = 1.21615. Apply it once to a 20 °C resistance. Do not apply it again to a resistance already stated at 75 °C. The 2% stranding allowance is a concentric-lay estimate, not a bound for every cable construction.

Calculated DC resistance, Ω per 1,000 ft of one conductor at 75 °C
AWGSolidStranded estimate
187.76517.9204
164.88354.9812
143.07133.1327
121.93161.9702
101.21481.2391

These are our computed NBS-based values, not NEC table entries. Display values are rounded; circuit calculations retain full precision.

Design assumptions and limits

System Sensor's historical example starts at 20.4 V. The editable input lets you check that example condition; it is not a universal NAC output rating. Confirm it for your equipment and end-of-discharge condition. This tool subtracts cable loss only; enter the available NAC terminal voltage after any internal panel losses. A 24 V nominal source is not a worst-case supply guarantee.

The lumped result is conservative for placement of the entered fixed current on the stated radial run. It does not account for voltage-dependent current, inrush, synchronization modules, connection losses, power-supply regulation, return-fed Class A operation, or additional branches. Use the device's listed maximum current for the applicable settings and waveform.

Check against your project's specifications and the AHJ / your procedure. A pass means only that this simplified voltage estimate meets your entered minimum. Confirm circuit current limits, maximum device voltage, conductor suitability, equipment compatibility, manufacturer instructions and the required design method separately.

For related circuit concepts, read the NAC vs SLC guide. Use the fire alarm battery calculator for the separate capacity calculation.

The ×1.02 stranded estimate can be slightly non-conservative: it can understate resistance, understate voltage drop and overstate maximum length. The 14 AWG comparison is about 0.3% below the matching NFPA 70 Chapter 9, Table 8 value. Use the specified cable resistance for design; a near-boundary pass in this tool is insufficient.

Common voltage drop mistakes

  • Entering the round trip. The calculator already doubles the one-way length. An out-and-back figure doubles the drop again.
  • Checking 24 V only. Nominal voltage is not the battery condition. Run the battery check with the end-of-discharge voltage from your panel or power supply manual.
  • Using typical appliance current. Strobes draw more as voltage falls. Use the maximum listed current for the candela, tone and waveform you will install.
  • Judging by percentage. The pass test is volts at the last appliance against its listed minimum. On a mixed circuit, use the highest minimum; a sync module can raise it.
  • Measuring on the floor plan. Straight-line distance misses risers, drops to each appliance and routing around obstructions. Use the cable route.
  • Using the even-spacing shortcut on an uneven circuit. The distributed estimate assumes equal currents at equal spacing. Otherwise use the lumped result or a segment-by-segment calculation.
  • Assuming Class A halves the drop. After an open, the far appliances can be fed from the return end over the whole route. Check the panel manual's method; this calculator models one radial run.

Voltage drop is one of three NAC checks. Size the standby batteries with the battery calculation method, and pick the cable rating from the FPL, FPLR and FPLP cable types guide.

Fire alarm voltage drop FAQ

How do you calculate voltage drop on a fire alarm NAC circuit?

Double the one-way length, because current goes out on one conductor and back on the other. Multiply that by the conductor's resistance per foot to get the loop resistance, then multiply by the total alarm current to get the drop in volts. Subtract the drop from the voltage at the NAC terminals and compare what is left with the lowest voltage the appliances are listed to run on.

What is the maximum voltage drop allowed on a fire alarm circuit?

This calculator does not apply a percentage cap. It checks whether the last appliance still gets at least its listed minimum operating voltage under the supply condition you enter. A project specification or your AHJ can add its own percentage or volt limit on top, so check the submittal checklist for the job.

Why start the calculation at 20.4 V instead of 24 V?

24 V is a nominal rating. Running on standby batteries near the end of their discharge, the panel delivers less, and System Sensor's voltage drop example starts at 20.4 V for that condition. Use the figure from your own panel or power supply manual and check both conditions; with the same load, the lower source voltage is the one that decides. Secondary power is covered in NFPA 72 (2022) §10.6.7.

Do I enter one-way or round-trip length?

One-way: the routed cable length from the NAC terminals to the last appliance. The calculator doubles it for the return conductor. Entering an out-and-back distance doubles the drop a second time.

Where does the wire resistance come from?

The calculator computes ideal copper resistance at 75 °C from NBS Handbook 100, shown in the reference table on this page. For a project calculation, use the cable manufacturer's published resistance or your own copy of NFPA 70, Chapter 9, Table 8. If your cable's resistance is higher than ours, this calculator understates the drop.

What wire size do I need for a NAC circuit?

This calculator checks the gauge you pick and reports the longest one-way run that still passes. Try the next size up if a run fails. The Alarm Ladder wire size calculator works it the other way round and finds the smallest AWG from 18 to 10 that passes your voltage checks. Cable type, such as FPL, FPLR or FPLP, is a separate choice under NFPA 70 Article 760.

Get the cable voltage loss on a notification circuit and a PASS or FAIL against your minimum, with a printable worksheet. A study aid; your own documents, procedures and the AHJ govern real work.

Try one free question

Try one question

Question 1 of the free 10-question check on NICET FA II. No signup. Then ask Strobe, the AI study assistant, why the answer is right and the others are wrong.

Question 1 of 10 · free checkUntimed

Submittal Preparation and System Layout

Which shop drawing best shows how panels, power supplies and circuits connect between floors?

Press A-D or 1-4 to choose an answer while this question is on screen.

Choose an answer to begin

Email me the free NICET FA II exam-day kit

What to bring, arriving and the testing room, plus the booking steps, from the exam body's own candidate guide. Sent to your inbox.

Ask Strobe before you buy AI your AI study assistant

See what's on the NICET FA II exam, test yourself with 5 quick questions, or find the plan that fits you.

Terms this tool uses

Sources

Print the Fire alarm voltage drop and battery formula sheet (free PDF, one page) and the worked guide.

Preparing for NICET Fire Alarm Systems Level II?

You just checked the voltage left at the end of your NAC circuit. The free 10-question check shows which Level II topics to fix first, no signup. The Alarm Ladder course drills them and explains every answer.

Take the free 10-question NICET FA II check

Read the Level II exam guide

The NICET FA II course

Available now · instant access

The NICET FA II course

  • 12modules of lessonsEvery task on the outline
  • 2full-length timed exams110 questions in 155 minutes each
  • 471practice questionsEach one explained
  • 8worked calculationsStep by step
  • 30code-navigation drillsFind it fast in NFPA 72
  • 1week-by-week study planSet to your exam date

Turn a practice answer into a study step. In untimed practice, ask Strobe AI about any question you answer, follow up, then see your weakest topics and what to drill next.

Level II course$149

Terms and refunds · Secure checkout by Stripe · Billed by Nori Software

See the course

Compare plans

Every answer comes with a full explanation.

Add this calculator to your site

Copy this HTML into your page. Keep the attribution link. The frame scrolls to show the full calculator and explanation; no external script is needed.