Fire alarm wire size calculator: the smallest gauge that keeps every device in range

Enter your alarm load and one-way cable length to compare solid and stranded copper in AWG 18, 16, 14, 12 and 10. The calculator highlights the physically smallest wire that meets your entered device minimum plus optional voltage headroom in every enabled supply check.

Download current inputs, the device list and all gauge results as a free CSV spreadsheet for Excel, Google Sheets or Numbers.

By the Alarm Ladder editorial team.

Exports your current inputs and every size compared, ready to keep or share.

Circuit inputs

Results update as you type. Use listed maximum alarm current for the selected device settings and supply waveform. 1 mA = 0.001 A.

24 V is a nominal starting value. Enter available NAC terminal voltage for the operating condition being checked.

16 V is an editable example, not a universal requirement. For mixed devices, use the highest listed minimum.

Default 0 V. All pass/fail checks and maximum lengths include this extra voltage margin. Minimum plus headroom must be at most 100 V.

20.4 V is a common end-of-discharge design value. Enter the voltage at the NAC terminals after panel and power-supply losses, not the raw battery voltage.

Requires equal-current devices at L/N, 2L/N, …, L from the source. Mixed currents or unequal spacing need a segment-by-segment calculation.

Tool ranges: 0–100,000 ft (0–30,480 m), 0–100 A, voltages above 0 up to 100 V, and up to 10,000 devices in 100 groups. These are input limits, not equipment ratings.

Calculated results

Total load: 1.5 A. Required last-device voltage: 16 V (minimum plus headroom).

Model: All load at the end (conservative for this radial run).

Smallest passing solid copper: 18 AWG
Meets all enabled voltage checks plus headroom only. Lower AWG numbers mean larger conductors.

Smallest passing stranded copper: 18 AWG
Meets all enabled voltage checks plus headroom only. Lower AWG numbers mean larger conductors.

Studying for NICET FA II? Take the free 10-question check to see exactly which topics to fix first, then close the gaps with the Alarm Ladder course.

Or read a full free lesson first (no signup).

Studying with a coworker? Send them the free check.

Unrounded values determine pass/fail. Displayed values are rounded to 3 decimal places. Max lengths are one way and include headroom; 0 can mean no feasible length.

16 AWG solid copper

PASS for all enabled checks

4.884 Ω/1,000 ft per conductor at 75 °C

Source check (24 V)
19.605 V at last device · PASS
Source max length
546.051 ft
Combined max length
546.051 ft

16 AWG stranded copper

PASS for all enabled checks

4.981 Ω/1,000 ft per conductor at 75 °C

Source check (24 V)
19.517 V at last device · PASS
Source max length
535.344 ft
Combined max length
535.344 ft

14 AWG solid copper

PASS for all enabled checks

3.071 Ω/1,000 ft per conductor at 75 °C

Source check (24 V)
21.236 V at last device · PASS
Source max length
868.255 ft
Combined max length
868.255 ft

14 AWG stranded copper

PASS for all enabled checks

3.133 Ω/1,000 ft per conductor at 75 °C

Source check (24 V)
21.181 V at last device · PASS
Source max length
851.231 ft
Combined max length
851.231 ft

12 AWG solid copper

PASS for all enabled checks

1.932 Ω/1,000 ft per conductor at 75 °C

Source check (24 V)
22.262 V at last device · PASS
Source max length
1,380.58 ft
Combined max length
1,380.58 ft

12 AWG stranded copper

PASS for all enabled checks

1.97 Ω/1,000 ft per conductor at 75 °C

Source check (24 V)
22.227 V at last device · PASS
Source max length
1,353.51 ft
Combined max length
1,353.51 ft

10 AWG solid copper

PASS for all enabled checks

1.215 Ω/1,000 ft per conductor at 75 °C

Source check (24 V)
22.907 V at last device · PASS
Source max length
2,195.208 ft
Combined max length
2,195.208 ft

10 AWG stranded copper

PASS for all enabled checks

1.239 Ω/1,000 ft per conductor at 75 °C

Source check (24 V)
22.885 V at last device · PASS
Source max length
2,152.165 ft
Combined max length
2,152.165 ft

Battery-condition check is off. Turn it on to size wire for end of discharge too.

How to calculate NAC wire size

Start with the device minimum, the lowest available NAC terminal voltage and the complete alarm load. Set headroom deliberately; it adds to the required device voltage. This reverses a voltage-drop check: calculate each candidate gauge, then choose the smallest conductor meeting the required voltage. A lower AWG number means a larger conductor. Let L be one-way length in feet, r be resistance of one conductor in Ω/1,000 ft, I be total fixed alarm current in A, Vₛ be available NAC terminal voltage, Vₘᵢₙ be the listed device minimum and H be your headroom in V.

  • Required voltage: Vᵣ = Vₘᵢₙ + H.
  • Loop resistance: R = 2 × L × r ÷ 1,000.
  • Voltage drop: ΔV = I × R. Last-device voltage: Vₗₐₛₜ = Vₛ − ΔV.
  • Pass: Vₗₐₛₜ ≥ Vᵣ in both the source and optional battery-condition checks.
  • Maximum one-way length: Lₘₐₓ = 1,000 × (Vₛ − Vᵣ) ÷ (2 × I × r), for I > 0 and Vₛ ≥ Vᵣ.

The cable-loss equations apply System Sensor's voltage-drop example, p. 4 to outgoing and return conductors. Convert meters to feet by dividing by 0.3048. Combined maximum length is the lower limit from the enabled supply checks. A source below Vᵣ means no feasible length; zero current produces no finite voltage-drop limit.

Optional point-to-point mode

For N equal-current devices equally spaced at L/N, 2L/N, …, L, each segment carries its downstream load. Our sum of these segment drops gives ΔVpoint = ΔVend × (N + 1)/(2N). Divide the end-load maximum length by the same factor. With ten devices the drop factor is 0.55; with one it is 1.

This is an algebraic extension of the I × R method: add each segment's loss using only its downstream current. Mixed currents, unequal spacing, branches or return-fed operation need an actual circuit-specific calculation.

Worked example: which gauge passes?

Take 1.5 A, a 300 ft one-way run, 24 V at the source, an enabled 20.4 V battery-condition check, a 16 V device minimum and 0 V headroom. With all load at the end, 18 AWG solid gives 20.4 − (2 × 300 × 7.765145 × 1.5 ÷ 1,000) ≈ 13.411 V on battery, so it fails. 16 AWG solid gives approximately 16.005 V and passes; its battery-limited maximum length is approximately 300.328 ft.

16 AWG stranded gives approximately 15.917 V and fails, so the smallest passing stranded option is 14 AWG, at approximately 17.581 V. Adding 0.5 V headroom raises the required voltage to 16.5 V, so 14 AWG becomes the smallest passing size for both constructions. All comparisons use full precision.

Resistance assumptions

Resistance comes from ideal annealed, uncoated copper geometry and constants in National Bureau of Standards (hosted by NIST), Copper Wire Tables, Handbook 100 (1966), §2.2 and appendices 4–5. We calculate at 75 °C and add 2% for the concentric-lay stranded estimate. Confirm actual resistance with the cable manufacturer; construction and tolerances vary. The temperature assumption does not establish cable suitability.

d(mm) = 0.127 × 92^((36 − AWG)/39); A = πd²/4; r₂₀ = (1/58) × 304.8/A; r₇₅ = r₂₀ × [1 + 0.00393 × (75 − 20)].

For comparison with your code book, use NFPA 70-2020, Chapter 9, Table 8 and its notes. Match copper coating, stranding, temperature and units. The numbers here remain NBS-derived estimates, not NEC entries. The temperature multiplier is 1.21615 from 20 °C to 75 °C; do not correct a 75 °C resistance a second time.

The 16 AWG solid example passes by only about 0.005 V. Treat that as a boundary result: a cable-specific resistance or additional loss can change the selection. Rerun the check with the specified cable data and supply condition before choosing a conductor.

Wire size is more than voltage drop

A passing voltage estimate alone does not select an approved cable. Check the panel's NAC current rating, permitted conductor sizes and terminal range, cable listing (FPL/FPLR/FPLP), mechanical and installation requirements, and the manufacturer's instructions. Consult NFPA 70-2020 Article 760 and the adopted NFPA 72 edition for your project; no standard text or tables are reproduced here.

An SLC has different equipment-specific limits. Use the NAC vs SLC guide to understand the distinction.

Enter listed maximum alarm currents for the chosen settings and waveform. This fixed-current two-wire radial estimate excludes inrush, voltage-dependent current, connection and module losses, supply regulation and additional branches. Check maximum device voltage separately. Enter voltage available at NAC terminals after panel losses; raw battery voltage can overstate the available supply. The editable 20.4 V starting point comes from System Sensor's historical worked example; confirm the available output for your equipment.

Check against your code edition, procedure and the responsible inspector/engineer. This calculation aid is an engineering estimate, not design approval. Confirm project specifications and the AHJ's requirements.

For an individual gauge, use the fire alarm voltage-drop calculator. Read the voltage-drop formula guide for the method.

The ×1.02 stranded estimate can be slightly non-conservative: it can understate resistance, understate voltage drop and overstate maximum length. The 14 AWG comparison is about 0.3% below the matching NFPA 70 Chapter 9, Table 8 value. Use the specified cable resistance for design; a near-boundary pass in this tool is insufficient.

Fire alarm wire size calculator FAQ

How do I find the smallest wire gauge for an NAC circuit?

Work out the drop for each gauge, then take the smallest one that keeps the last device at or above the required voltage. The drop is ΔV = I × R, where R = 2 × L × r ÷ 1,000, L is the one-way length in feet and r is the resistance of one conductor in Ω per 1,000 ft. Take 1.5 A, a 300 ft one-way run, 24 V at the source, a 20.4 V battery-condition check and a 16 V device minimum. 18 AWG solid leaves about 13.411 V on battery and fails. 16 AWG solid leaves about 16.005 V and passes.

Why can stranded wire need a bigger gauge than solid?

The calculator adds 2% to the solid resistance as a stranded estimate. In the same example 16 AWG stranded leaves about 15.917 V on battery and fails, so the smallest passing stranded size is 14 AWG, at about 17.581 V. The 2% is an estimate and can slightly understate resistance, so use the resistance of the cable you specify.

What does headroom do?

Headroom is extra voltage you want above the device minimum. It adds to the required voltage, so a 16 V minimum plus 0.5 V of headroom needs 16.5 V at the last device. In the example 16 AWG solid then fails, and 14 AWG is the smallest passing size for both solid and stranded.

If a gauge passes, is it the right cable for the job?

Not by itself. This is a voltage estimate only. 16 AWG solid passes the example by about 0.005 V, and its battery-limited maximum length is about 300.328 ft against a 300 ft run, so a cable-specific resistance can change the pick. The panel's NAC current rating, terminal range, cable listing and installation requirements still apply. Check the manufacturer's listed data and the AHJ.

Audible output is a separate check from NAC wire size

The controls above check NAC cable loss. For a NICET Fire Alarm Systems Level II sound problem, first decide whether you are changing one source's level, combining sources at one listener, or changing the distance to one source. System Sensor's Voice Evacuation Systems Applications Guide, §3, printed pp. 3–4 explains power ratios, level addition and distance loss.

For a power ratio, ΔdB = 10 × log10(P2/P1). For the energy-sum estimate of uncorrelated sound sources measured at the same listener, with matching weighting and reference, convert each level back to a relative energy, add, then take the logarithm:

Ltotal = 10 × log10(10^(L1/10) + 10^(L2/10) + …)

Two sources each contributing 70 dB at that listener give 73.0103 dB. The increase is about 3 dB. This energy sum does not predict phase interference between coherent tones; it is not a guaranteed gain from adding another alarm appliance.

For a point-source free-field estimate at unchanged output, intensity varies as 1/r². The level change is L2 − L1 = −20 × log10(r2/r1), with both distances in the same units and measured from the source. Doubling distance gives a 6.0206 dB loss; intensity falls to one-quarter. This is the origin of the approximate 6 dB distance rule.

Apply the distance model only where free-field point-source assumptions hold. Walls, reflections and speaker directionality change a room's result. Do not use this model as a UT echo-distance correction or as proof of audibility in a building.

Look up the audibility margin separately

For NFPA 72-2022, use §18.4.4.1 for public-mode audibility, §18.4.5.1 for private-mode audibility and §18.4.6 for sleeping areas. Read the full applicable section in your own code copy before selecting the target. A calculated SPL is only an estimate to compare with that target; it does not supply the code margin or replace field measurements.

Compare solid and stranded copper from AWG 18 to 10 and see the smallest wire that meets your voltage checks. A study aid; your own documents, procedures and the AHJ govern real work.

Try one free question

Try one question

Question 1 of the free 10-question check on NICET FA II. No signup. Then ask Strobe, the AI study assistant, why the answer is right and the others are wrong.

Question 1 of 10 · free checkUntimed

Submittal Preparation and System Layout

Which shop drawing best shows how panels, power supplies and circuits connect between floors?

Press A-D or 1-4 to choose an answer while this question is on screen.

Choose an answer to begin

Email me the free NICET FA II exam-day kit

What to bring, arriving and the testing room, plus the booking steps, from the exam body's own candidate guide. Sent to your inbox.

Ask Strobe before you buy AI your AI study assistant

See what's on the NICET FA II exam, test yourself with 5 quick questions, or find the plan that fits you.

Terms this tool uses

Sources

Print the Fire alarm voltage drop and battery formula sheet (free PDF, one page) and the worked guide.

Preparing for NICET Fire Alarm Systems Level II?

You just found the wire size that keeps your NAC circuit inside its voltage limits. The free 10-question check shows which Level II topics to fix first, no signup. The Alarm Ladder course drills them and explains every answer.

Take the free 10-question NICET FA II check

The NICET FA II course

Available now · instant access

The NICET FA II course

  • 12modules of lessonsEvery task on the outline
  • 2full-length timed exams110 questions in 155 minutes each
  • 471practice questionsEach one explained
  • 8worked calculationsStep by step
  • 30code-navigation drillsFind it fast in NFPA 72
  • 1week-by-week study planSet to your exam date

Turn a practice answer into a study step. In untimed practice, ask Strobe AI about any question you answer, follow up, then see your weakest topics and what to drill next.